12V vs 15V Landscape Transformer Taps

Higher taps can offset voltage drop on a low-voltage run. They are not a universal 15 V setting, and EMCOD families do not all print the same tap set.

Written by Projekt Supply Lighting Team. Last reviewed September 17, 2026. First published September 17, 2026. Part of the EMCOD LED driver and transformer guide.

Why landscape transformers have multiple taps

  • Many low-voltage landscape fixtures are designed around a nominal 12 V operating window.
  • Cable resistance drops voltage as current travels. The voltage that matters is at the fixture, not only at the transformer terminal.
  • A higher tap raises starting voltage so a long or loaded run can still arrive inside the fixture window.
  • The correct tap depends on actual load, conductor, length, and fixture limits. It is not “long run = highest tap.”
  • Measure voltage at the load after install. Do not assume the tap label equals fixture voltage.

Nominal 12 V landscape systems

Many landscape fixtures are specified around a 12 V operating window. A 15 V transformer terminal is not “brighter 12 V.” It is extra starting voltage that can be consumed by cable drop. If the fixture then receives more than its manufacturer allows, it can run hot or fail. Check voltage at the load.

EMCOD family evidence — not a universal tap set

Public family pages publish spec-sheet tap voltages for sourced MPNs. Do not copy one MPN’s tap set onto every model in the family.

Sourced tap evidence for ESL, Simple, EMT, and SMT. Confirm the selected MPN sheet.
FamilySourced tap evidenceEvidence note
ESL12 VAC and 15 VAC on sourced ESL75W / ESL100W sheetsESL100W spec: magnetic; timer and photocell build-in options; 12/15 VAC taps.
Simple Series12 VAC and 15 VAC on the sourced SS120W sheetSS120W spec: magnetic; timer and photocell build-in options; 12/15 VAC taps; 120 W max.
EMTEMT-E: 12/13/14/15 VAC. EMT-22E tap sets vary by MPN; use the selected spec.EMT150SS-E / EMT300SS-E / EMT600SS-E spec: 12/13/14/15 VAC. EMT300SS-22E spec: 12.8/15.2/17.2/22.2 VAC. Timer and photocell build-in options.
SMTInstall: 12 V, 13 V, or 15 V taps in each of three zonesSMT300W spec: 300 W max, 100 W per circuit. Install: Wi-Fi 2.4 GHz, Tuya/Smart Life, three zones, app timer.
  • Public PDPs publish spec-sheet tap voltages for sourced MPNs. Do not copy a sibling MPN’s tap set onto every EMT model.
  • Sourced ESL and Simple sheets print 12 VAC and 15 VAC. That is manufacturer-sheet evidence for those cited documents, not a claim that every landscape transformer has only those two taps.
  • EMT-E sourced sheets print 12/13/14/15 VAC. EMT-22E sourced sheets print a 12–22 VAC set. Those are different products.
  • SMT install documentation lists 12/13/15 V per zone. Confirm the selected SMT MPN install sheet.

Exact models used as identification examples: ESL100W (sourced ESL sheet prints 12/15 VAC), EMT300SS-E (do not invent this MPN’s tap voltages from a sibling), EMT300SS-22E (sourced 12–22 VAC set), and SMT300W (install lists 12/13/15 V per zone). Source: EMCOD manufacturer specifications

Check voltage at the load

Choose a tap so the fixture voltage stays inside that fixture’s published window after drop. Nearby fixtures on a short run can see nearly the tap voltage. Far fixtures see less. The correct tap is a field and design result, not a catalog slogan.

Capacity and family architecture: How to Choose and Size a Landscape Lighting Transformer. Families: ESL, Simple, EMT, SMT.

Voltage-drop calculation

This page does not repeat the wire-gauge arithmetic. Use Landscape Lighting Voltage Drop for current, conductor resistance, and worked examples.

Common questions

Does every EMCOD landscape transformer have 12 V and 15 V taps?

No. Confirm the exact MPN specification or installation sheet. Sourced ESL and Simple sheets print 12/15 VAC. EMT-E sheets print 12/13/14/15 VAC. EMT-22E tap sets vary by MPN. SMT300W prints 12/13/15 VAC.

Should I use the 15 V tap on a long run?

Only if the voltage at the fixture stays inside that fixture’s window after drop. A higher tap can overvoltage nearby fixtures. Check the run, load, cable, and field voltage. Use the voltage-drop guide for the calculation.

Can I read EMT300SS-E taps from the model number?

No. EMT wattage class and stainless family are encoded; exact tap voltages are on the specification sheet. Do not assume EMT300SS-E uses the EMT-22E 12–22 VAC set.

Families and exact models this published guide actually covers. Family links are canonical product records. Exact models use machine-addressable ?variant= URLs.

  • EMCOD ESL LED Drivers

    Landscape transformer. Landscape transformer family whose sourced sheets document tap options. Confirm the selected MPN.

  • EMCOD Simple LED Drivers

    Landscape transformer. Landscape transformer family whose sourced sheets document tap options. Confirm the selected MPN.

  • EMCOD EMT LED Drivers

    Landscape transformer. Multi-tap landscape family. EMT-E sheets print 12/13/14/15 VAC; EMT-22E tap sets vary by MPN.

  • EMCOD SMT LED Drivers

    Landscape transformer. Landscape transformer family whose sourced sheets document tap options. Confirm the selected MPN.

Exact models referenced

  • EMCOD ESL100W

    Landscape transformer in ESL. Sourced ESL sheet prints 12/15 VAC taps.

  • EMCOD EMT300SS-E

    Landscape transformer in EMT. EMT300SS-E spec prints 12/13/14/15 VAC. Do not read taps from the MPN alone.

  • EMCOD EMT300SS-22E

    Landscape transformer in EMT. Sourced 12–22 VAC tap-set contrast to EMT-E.

  • EMCOD SMT300W

    Landscape transformer in SMT. SMT install lists 12/13/15 V per zone; confirm the selected sheet.

Technical Sources & References

  1. EMCOD Lighting Group — ESL100W specification sheetManufacturer specification sheet
  2. EMCOD Lighting Group — EMT150SS-E specification sheetManufacturer specification sheet
  3. EMCOD Lighting Group — EMT300SS-22E specification sheetManufacturer specification sheet
  4. EMCOD Lighting Group — SMT300W installation instructionsManufacturer installation instructions
  5. Projekt Supply catalog / EMCOD Lighting Group — EMT Series familyManufacturer catalog / Projekt catalog record

Projekt Supply technical guides are based on manufacturer-published specifications, installation documentation and independent technical references. Product specifications can change. Always verify the current specification sheet and installation instructions for the exact product before purchase or installation. This guide is not a substitute for electrical code, manufacturer instructions, or licensed electrical work.